TexasHVACExam

Sample questions: air conditioning and refrigeration contractor exam

TexasHVACExam · Topics · Exam guide · Sample questions

Practice questions written by us, with the correct answer and the rule cited. They are not official questions.

1. A cooling load calculation shows a sensible load of 36,000 Btu/h. The return air is 75°F, the supply air is 55°F, and the outdoor design temperature is 95°F. Using sensible heat = 1.08 x CFM x delta-T, what supply airflow is required, to the nearest 10 CFM?

  1. 400 CFM
  2. 830 CFM
  3. 1,670 CFM
  4. 2,650 CFM

CFM = 36,000 / (1.08 x 20°F) = 1,667, or 1,670 CFM. A result of 400 CFM divides by the total-heat constant 4.5 instead of 1.08; 830 CFM uses the outdoor-to-supply difference of 40°F instead of the room-to-supply temperature difference; 2,650 CFM uses the latent-heat constant 0.68.

2. What capacity limits apply to a Class B air conditioning and refrigeration contractor license under Texas Occupations Code §1302.253(c)?

  1. Not more than 15 tons cooling or 1.0 million Btu/h heating
  2. Not more than 25 tons cooling or 1.5 million Btu/h heating
  3. Not more than 25 tons cooling or 2.5 million Btu/h heating
  4. Not more than 50 tons cooling or 3.0 million Btu/h heating

Texas Occupations Code §1302.253(c) limits a Class B license to a system, a product, or equipment of not more than 25 tons cooling capacity or 1.5 million British thermal units per hour output heating capacity. The 15-ton and 1.0 million pair understates both limits, 2.5 million overstates the heating limit, and the 50-ton and 3.0 million pair doubles both; a Class A license, by contrast, has no size limit under §1302.253(b).

3. An R-410A split system with a piston metering device shows a low suction pressure, a low discharge pressure, a superheat of 28°F, a subcooling of 3°F, and compressor current below nameplate. Airflow is normal and the filter is clean. Which condition is MOST likely?

  1. Dirty condenser coil with low airflow
  2. Overcharge of refrigerant from topping off
  3. Restricted liquid line filter drier
  4. Low refrigerant charge from a leak

Low pressures with high superheat and low subcooling show that too little refrigerant is reaching the evaporator and the condenser holds little liquid, which is the undercharge pattern. A dirty condenser and an overcharge both raise discharge pressure, and a restricted filter drier raises subcooling instead of lowering it.

4. Lone Star Comfort Systems installs a natural-draft gas furnace in a small closet with a solid door and no openings to other spaces or to the outdoors. What is the most direct concern?

  1. The closet cannot supply enough air, so the burner can produce carbon monoxide
  2. The furnace will get too much air, so the burner flames will lift off the ports
  3. The closet will become too humid, so the blower motor bearings will fail early
  4. The gas supply pressure will rise, so the pilot will trip the high-limit switch

A tight closet is a confined space: its small volume and lack of openings cannot supply the air the furnace needs, so combustion is incomplete and carbon monoxide can be produced. Too much air, humidity damage to the blower bearings, and a higher gas supply pressure are not effects of a closed closet.

5. Lone Star Comfort Systems installs a 5-ton air conditioner in a Houston home whose calculated load is 3 tons. The thermostat is satisfied after short runs, and the owner reports clammy indoor air. What is the most likely cause?

  1. The condensate trap is too deep, so water cannot leave the drain pan
  2. The unit is undersized, so it runs nonstop and cannot reach dew point
  3. The condenser is dirty, so the coil stays above the dew point
  4. The unit is oversized, so short cycles remove too little moisture

A 5-ton unit on a 3-ton load is oversized: it satisfies the thermostat quickly, and short cycles end before the coil has removed much moisture, so the latent load is left behind. An undersized unit would run long and dehumidify more, and neither a deep trap nor a dirty condenser explains short runs with a satisfied thermostat.

6. Alamo Air & Cold holds a Class A license with only an environmental air conditioning endorsement. A grocery customer asks it to install a walk-in freezer. Under Texas Occupations Code §1302.254, which statement is correct?

  1. A Class A license covers commercial refrigeration without an additional endorsement
  2. It needs the commercial refrigeration and process cooling or heating endorsement added
  3. A certified technician on staff can cover the missing endorsement for the company
  4. Contractors of the same class may work on either type of system without a change

Texas Occupations Code §1302.254(d) bars a license holder from contracting in a type of work for which the license is not endorsed, and §1302.254(c) provides the commercial refrigeration and process cooling or heating endorsement for that type. A Class A license under §1302.253(b) removes the size limit only for the types endorsed on it. A technician's certification does not add an endorsement to the contractor's license.

7. A combustion analysis of a gas furnace shows carbon monoxide well above the allowable limit. What does this MOST likely indicate?

  1. Incomplete combustion, such as flame impingement or sooting
  2. Complete combustion with a large amount of excess air
  3. A temperature rise that is above the nameplate range
  4. A flue gas temperature that is low enough to condense

Elevated CO is a product of incomplete combustion, which can come from flame impingement, a dirty or misadjusted burner, or too little combustion air. Complete combustion produces carbon dioxide and water vapor with little or no CO, so a high CO reading rules it out; temperature rise is an airflow measurement, and a low flue temperature relates to condensation, not to CO production.

8. What happens to the refrigerant in the first section of a condenser coil, called the desuperheating zone?

  1. Superheated vapor is cooled down to its saturation temperature
  2. Saturated liquid is cooled further below its saturation temperature
  3. Saturated vapor condenses to liquid at a constant temperature
  4. Liquid refrigerant flashes into vapor as its pressure drops

In the desuperheating zone the hot discharge vapor gives up sensible heat until it reaches its saturation temperature. Cooling saturated liquid below saturation is the subcooling zone at the end of the coil. Condensing at a constant temperature is the middle zone. Flashing into vapor as pressure drops happens at the metering device, not in the condenser.

9. A technician will pressure test a new refrigerant circuit from a cylinder fitted with a pressure regulator and a relief device. Which gas should be used?

  1. Pure oxygen from a cylinder
  2. Acetylene from a cylinder
  3. Compressed air from a shop line
  4. Dry nitrogen from a cylinder

Dry nitrogen is inert and is the standard test gas when supplied through a regulator with a relief device. Oxygen can ignite violently on contact with oil, acetylene is a fuel gas that becomes unstable under pressure, and shop air carries moisture and oxygen that contaminate the system and add a fire risk.

10. A rooftop unit's compressor keeps shutting down on its high-pressure switch. Which troubleshooting action is NOT acceptable?

  1. Checking the condenser coil and the condenser fan motor operation
  2. Reading the suction and discharge pressures with a gauge manifold
  3. Jumping out the high-pressure switch so the compressor keeps running
  4. Confirming that the refrigerant charge matches the unit specifications

A high-pressure switch is a safety control that protects the compressor and system from excessive discharge pressure, so it must not be bypassed to keep the unit running; the cause of the high pressure has to be found and corrected. Inspecting the condenser coil and fan, reading system pressures, and verifying the charge are all normal ways to find that cause.

11. Under 16 TAC §75.100, which work on an air distribution system requires a contractor license under Texas Occupations Code Chapter 1302?

  1. System testing of the air distribution system
  2. Biomedical testing of the air distribution system
  3. Duct cleaning within the §75.100(c)(1) limits
  4. System balancing of the air distribution system

Correct answer: D) System balancing of the air distribution system. The full explanation, with the rule it comes from and why each other option is wrong, is included with Premium access.

12. A load calculation gives a total cooling load of 42,000 Btu/h. Using 12,000 Btu/h per ton, what is the load in tons of cooling?

  1. 3.5 tons
  2. 4.2 tons
  3. 12.3 tons
  4. 35.0 tons

Correct answer: A) 3.5 tons. The step-by-step working, and the mistake behind each wrong option, are in the full explanation included with Premium access.

13. An R-410A split system has a suction pressure of 118 psig and a suction line temperature of 52°F at the service valve. Use the saturation (dew point) temperature of R-410A at that pressure. What is the system superheat, rounded to the nearest °F?

  1. 6°F
  2. 12°F
  3. 19°F
  4. 40°F

Correct answer: B) 12°F. The step-by-step working, and the mistake behind each wrong option, are in the full explanation included with Premium access.

14. A mechanical room is 30 ft long, 20 ft wide and 12 ft high. An exhaust fan moves 1,800 CFM. How many air changes per hour does the fan provide?

  1. 0.25 air changes per hour
  2. 15 air changes per hour
  3. 180 air changes per hour
  4. 240 air changes per hour

Correct answer: B) 15 air changes per hour. The step-by-step working, and the mistake behind each wrong option, are in the full explanation included with Premium access.

15. A gas furnace has an input of 100,000 Btu/h and an efficiency of 80 percent. The measured temperature rise is 50°F. Using the 1.08 factor and rounding to the nearest whole CFM, what is the airflow?

  1. 356 CFM
  2. 1,185 CFM
  3. 1,481 CFM
  4. 1,852 CFM

Correct answer: C) 1,481 CFM. The step-by-step working, and the mistake behind each wrong option, are in the full explanation included with Premium access.

16. What is the main function of the reversing valve (four-way valve) in a heat pump?

  1. Reverses refrigerant flow so the two coils swap evaporator and condenser roles
  2. Meters liquid refrigerant into whichever coil is currently acting as the evaporator
  3. Holds back liquid refrigerant so it cannot reach the compressor suction inlet
  4. Maintains minimum condensing pressure when outdoor air temperatures are very low

Correct answer: A) Reverses refrigerant flow so the two coils swap evaporator and condenser roles. The full reasoning, and why each other option is wrong, is included with Premium access.

17. At sea level, how is absolute pressure (psia) found from a gauge reading in psig?

  1. Subtract atmospheric pressure of 14.7 psi from the gauge reading
  2. Multiply the gauge reading by atmospheric pressure of 14.7 psi
  3. Divide the gauge reading by atmospheric pressure of 14.7 psi
  4. Add atmospheric pressure of 14.7 psi to the gauge reading

Correct answer: D) Add atmospheric pressure of 14.7 psi to the gauge reading. The full reasoning, and why each other option is wrong, is included with Premium access.

18. Lone Star Comfort Systems replaces a 20 in. x 20 in. return grille with a smaller decorative grille on a system that moves the same airflow. The owner now reports a loud whistle at the grille. What is the most likely cause?

  1. High face velocity through the smaller free area of the grille
  2. Low face velocity causing the air to stall at the grille
  3. Excess throw from the grille reaching the opposite wall
  4. Too much induction of room air into the supply stream

Correct answer: A) High face velocity through the smaller free area of the grille. The full reasoning, and why each other option is wrong, is included with Premium access.

19. Which practice is NOT acceptable for a gravity condensate drain line serving an indoor cooling coil?

  1. Sloping the line downward along its full run to the point of disposal
  2. Supporting the line at intervals so that it cannot sag and hold water
  3. Providing a way to clear a clog in the line without cutting the pipe
  4. Running part of the line uphill before it reaches the point of disposal

Correct answer: D) Running part of the line uphill before it reaches the point of disposal. The full reasoning, and why each other option is wrong, is included with Premium access.

20. A condensing unit nameplate lists an MCA of 24 amps and an MOCP of 40 amps. Which statement correctly describes what these two ratings mean?

  1. MCA is the largest breaker or fuse; MOCP sizes the supply conductors
  2. MCA sizes the supply conductors; MOCP is the largest breaker or fuse
  3. MCA is the running current in test; MOCP is the locked-rotor current
  4. MCA is the starting current; MOCP is the smallest breaker permitted

Correct answer: B) MCA sizes the supply conductors; MOCP is the largest breaker or fuse. The full reasoning, and why each other option is wrong, is included with Premium access.

21. A customer wants to save money by connecting a new gas dryer's exhaust duct to the existing furnace flue instead of cutting a hole in the wall. What should the contractor advise?

  1. Connect it to the furnace flue, provided the flue is a masonry chimney
  2. Run it as a separate duct through an outside wall to the outdoors
  3. Connect it to the furnace flue, provided a backdraft damper is added
  4. Run it into the attic, provided a fine mesh lint screen is added

Correct answer: B) Run it as a separate duct through an outside wall to the outdoors. The full reasoning, and why each other option is wrong, is included with Premium access.

22. Which technician certification covers a person who works only on low-pressure appliances under 40 CFR 82.161(a)(1)?

  1. Type III technician
  2. Type I technician
  3. Type II technician
  4. MVAC technician

Correct answer: A) Type III technician. The full explanation, with the rule it comes from and why each other option is wrong, is included with Premium access.

23. A gas furnace with flame rectification lights normally, but the gas valve closes after about three seconds, and the board retries before locking out. The ignitor, inducer, and pressure switch work correctly. What is the MOST likely cause?

  1. A flame sensor that is coated with oxide
  2. A hot-surface ignitor that is burned out
  3. An inducer pressure switch that is stuck open
  4. A blower motor with a seized shaft bearing

Correct answer: A) A flame sensor that is coated with oxide. The full reasoning, and why each other option is wrong, is included with Premium access.

24. A 10-inch round duct carries 600 CFM. What is the air velocity in the duct, to the nearest 10 fpm?

  1. 280 fpm
  2. 860 fpm
  3. 1,100 fpm
  4. 4,400 fpm

Correct answer: C) 1,100 fpm. The step-by-step working, and the mistake behind each wrong option, are in the full explanation included with Premium access.

25. Which defrost method melts frost by stopping the compressor and letting above-freezing air in the box warm the coil?

  1. Electric heater defrost
  2. Hot gas defrost cycle
  3. Off-cycle (air) defrost
  4. Reverse-cycle defrost

Correct answer: C) Off-cycle (air) defrost. The full reasoning, and why each other option is wrong, is included with Premium access.

26. An electric strip heater element reads 14.4 ohms with the power off. It operates on 240 volts single-phase. Using P = V² / R, how much power does it draw?

  1. 17 W
  2. 1,000 W
  3. 3,456 W
  4. 4,000 W

Correct answer: D) 4,000 W. The step-by-step working, and the mistake behind each wrong option, are in the full explanation included with Premium access.

27. Which of the following is NOT an appropriate source of combustion air for a gas furnace in a utility room?

  1. Outdoor air brought in through a duct that terminates outside the building
  2. Air drawn from a bedroom or bathroom that opens into the utility room
  3. Outdoor air through a permanent opening in an exterior wall of the room
  4. Air from a large adjoining indoor space connected through permanent openings

Correct answer: B) Air drawn from a bedroom or bathroom that opens into the utility room. The full reasoning, and why each other option is wrong, is included with Premium access.

28. Within how many hours after the work-related death of an employee must an employer report the fatality to OSHA under 29 CFR 1904.39(a)(1)?

  1. 8 hours
  2. 24 hours
  3. 48 hours
  4. 72 hours

Correct answer: A) 8 hours. The full explanation, with the rule it comes from and why each other option is wrong, is included with Premium access.

29. A coil in a humid Gulf Coast home removes 18,000 Btu/h of sensible heat and 12,000 Btu/h of latent heat. What is its sensible heat ratio (SHR)?

  1. 0.40
  2. 0.60
  3. 0.67
  4. 1.50

Correct answer: B) 0.60. The step-by-step working, and the mistake behind each wrong option, are in the full explanation included with Premium access.

30. Under 29 CFR 1926.1053, how far above the upper landing surface must the side rails of a portable ladder extend when the ladder is used for access?

  1. At least 1 foot
  2. At least 2 feet
  3. At least 3 feet
  4. At least 4 feet

Correct answer: C) At least 3 feet. The full explanation, with the rule it comes from and why each other option is wrong, is included with Premium access.

31. What does the throw of a supply air outlet describe?

  1. The vertical distance the air drops below the outlet by the end of its travel
  2. The width of the air pattern measured at the end of its travel from the outlet
  3. The distance the air travels from the outlet before slowing to a set terminal velocity
  4. The ratio of room air drawn into the stream to the air leaving the outlet

Correct answer: C) The distance the air travels from the outlet before slowing to a set terminal velocity. The full reasoning, and why each other option is wrong, is included with Premium access.

32. A single-phase compressor motor reads 3.6 ohms from C to R and 11.8 ohms from C to S at room temperature. What reading should be expected from S to R?

  1. 2.8 ohms
  2. 8.2 ohms
  3. 11.8 ohms
  4. 15.4 ohms

Correct answer: D) 15.4 ohms. The step-by-step working, and the mistake behind each wrong option, are in the full explanation included with Premium access.

33. Where should a refrigeration machinery room's exhaust system discharge air that may contain escaped refrigerant?

  1. Into a corridor, where building air dilutes it before it spreads
  2. Into the return-air plenum so the air handler can dilute it
  3. To the outdoors, at a point where it cannot re-enter the building
  4. Into the attic above the room, where it can disperse safely

Correct answer: C) To the outdoors, at a point where it cannot re-enter the building. The full reasoning, and why each other option is wrong, is included with Premium access.

34. Lone Star Comfort Systems asks a technician to check the evaporator superheat on a split system with a piston metering device. Which comparison gives this superheat?

  1. Liquid line temperature compared with the high-side saturation temperature
  2. Discharge line temperature compared with the high-side saturation temperature
  3. Suction line temperature compared with the low-side saturation temperature
  4. Return air temperature compared with the low-side saturation temperature

Correct answer: C) Suction line temperature compared with the low-side saturation temperature. The full reasoning, and why each other option is wrong, is included with Premium access.

35. Which statement about a liquid receiver in a commercial refrigeration system is INCORRECT?

  1. It is installed in the liquid line downstream of the condenser outlet
  2. It stores refrigerant that is not needed when the evaporator load drops
  3. It helps keep a full column of liquid refrigerant at the expansion device
  4. It is placed in the suction line to guard the compressor against liquid

Correct answer: D) It is placed in the suction line to guard the compressor against liquid. The full reasoning, and why each other option is wrong, is included with Premium access.

36. A company that holds no contractor license offers to adjust the dampers and set the airflow at each register to design values. Under 16 TAC §75.100(f), how is this work classified?

  1. System testing, which may be performed without a license
  2. System balancing, which requires a Chapter 1302 license
  3. Duct cleaning, which may be performed without a license
  4. Biomedical testing, which may be performed without a license

Correct answer: B) System balancing, which requires a Chapter 1302 license. The full explanation, with the rule it comes from and why each other option is wrong, is included with Premium access.

37. An ice maker takes in 250 lb of water per hour at 52 °F, cools it to 32 °F, and freezes all of it into ice at 32 °F. Use 144 Btu/lb for freezing, a specific heat of 1 Btu per lb per °F for water, and 12,000 Btu/h per ton. What refrigeration load is required, in tons to one decimal?

  1. 0.4 tons
  2. 3.0 tons
  3. 3.4 tons
  4. 20.6 tons

Correct answer: C) 3.4 tons. The step-by-step working, and the mistake behind each wrong option, are in the full explanation included with Premium access.

38. A permit for a replacement system was issued on August 14, 2026, and the crew starts the work on September 21, 2026. Under 16 TAC §75.110(b), may the licensee complete this job under the 2021 code editions?

  1. No, because the crew started the work after September 1, 2026
  2. Yes, because the work was permitted before September 1, 2026
  3. Yes, once the municipality approves the late start of the work
  4. No, because the 2021 codes expired on August 31, 2026

Correct answer: B) Yes, because the work was permitted before September 1, 2026. The full explanation, with the rule it comes from and why each other option is wrong, is included with Premium access.

39. When a suction line includes a vertical riser, which design condition lets oil return to the compressor?

  1. Enough vapor velocity in the riser to sweep the oil upward
  2. A riser diameter taken from the compressor discharge connection
  3. A riser kept full of liquid refrigerant so that oil floats upward
  4. A riser sized for the lowest vapor velocity the system can reach

Correct answer: A) Enough vapor velocity in the riser to sweep the oil upward. The full reasoning, and why each other option is wrong, is included with Premium access.

40. Which practice is INCORRECT when installing a flexible duct run?

  1. Supporting the duct at regular intervals so it does not sag
  2. Installing the duct fully extended between connections
  3. Sealing the inner liner to each collar with approved tape
  4. Compressing extra length into the run to avoid cutting it

Correct answer: D) Compressing extra length into the run to avoid cutting it. The full reasoning, and why each other option is wrong, is included with Premium access.

Take the free test · full question bank and mock exams with a subscription