1. A cooling load calculation shows a sensible load of 36,000 Btu/h. The return air is 75°F, the supply air is 55°F, and the outdoor design temperature is 95°F. Using sensible heat = 1.08 x CFM x delta-T, what supply airflow is required, to the nearest 10 CFM?
CFM = 36,000 / (1.08 x 20°F) = 1,667, or 1,670 CFM. A result of 400 CFM divides by the total-heat constant 4.5 instead of 1.08; 830 CFM uses the outdoor-to-supply difference of 40°F instead of the room-to-supply temperature difference; 2,650 CFM uses the latent-heat constant 0.68.
2. What capacity limits apply to a Class B air conditioning and refrigeration contractor license under Texas Occupations Code §1302.253(c)?
Texas Occupations Code §1302.253(c) limits a Class B license to a system, a product, or equipment of not more than 25 tons cooling capacity or 1.5 million British thermal units per hour output heating capacity. The 15-ton and 1.0 million pair understates both limits, 2.5 million overstates the heating limit, and the 50-ton and 3.0 million pair doubles both; a Class A license, by contrast, has no size limit under §1302.253(b).
3. An R-410A split system with a piston metering device shows a low suction pressure, a low discharge pressure, a superheat of 28°F, a subcooling of 3°F, and compressor current below nameplate. Airflow is normal and the filter is clean. Which condition is MOST likely?
Low pressures with high superheat and low subcooling show that too little refrigerant is reaching the evaporator and the condenser holds little liquid, which is the undercharge pattern. A dirty condenser and an overcharge both raise discharge pressure, and a restricted filter drier raises subcooling instead of lowering it.
4. Lone Star Comfort Systems installs a natural-draft gas furnace in a small closet with a solid door and no openings to other spaces or to the outdoors. What is the most direct concern?
A tight closet is a confined space: its small volume and lack of openings cannot supply the air the furnace needs, so combustion is incomplete and carbon monoxide can be produced. Too much air, humidity damage to the blower bearings, and a higher gas supply pressure are not effects of a closed closet.
5. Lone Star Comfort Systems installs a 5-ton air conditioner in a Houston home whose calculated load is 3 tons. The thermostat is satisfied after short runs, and the owner reports clammy indoor air. What is the most likely cause?
A 5-ton unit on a 3-ton load is oversized: it satisfies the thermostat quickly, and short cycles end before the coil has removed much moisture, so the latent load is left behind. An undersized unit would run long and dehumidify more, and neither a deep trap nor a dirty condenser explains short runs with a satisfied thermostat.
6. Alamo Air & Cold holds a Class A license with only an environmental air conditioning endorsement. A grocery customer asks it to install a walk-in freezer. Under Texas Occupations Code §1302.254, which statement is correct?
Texas Occupations Code §1302.254(d) bars a license holder from contracting in a type of work for which the license is not endorsed, and §1302.254(c) provides the commercial refrigeration and process cooling or heating endorsement for that type. A Class A license under §1302.253(b) removes the size limit only for the types endorsed on it. A technician's certification does not add an endorsement to the contractor's license.
7. A combustion analysis of a gas furnace shows carbon monoxide well above the allowable limit. What does this MOST likely indicate?
Elevated CO is a product of incomplete combustion, which can come from flame impingement, a dirty or misadjusted burner, or too little combustion air. Complete combustion produces carbon dioxide and water vapor with little or no CO, so a high CO reading rules it out; temperature rise is an airflow measurement, and a low flue temperature relates to condensation, not to CO production.
8. What happens to the refrigerant in the first section of a condenser coil, called the desuperheating zone?
In the desuperheating zone the hot discharge vapor gives up sensible heat until it reaches its saturation temperature. Cooling saturated liquid below saturation is the subcooling zone at the end of the coil. Condensing at a constant temperature is the middle zone. Flashing into vapor as pressure drops happens at the metering device, not in the condenser.
9. A technician will pressure test a new refrigerant circuit from a cylinder fitted with a pressure regulator and a relief device. Which gas should be used?
Dry nitrogen is inert and is the standard test gas when supplied through a regulator with a relief device. Oxygen can ignite violently on contact with oil, acetylene is a fuel gas that becomes unstable under pressure, and shop air carries moisture and oxygen that contaminate the system and add a fire risk.
10. A rooftop unit's compressor keeps shutting down on its high-pressure switch. Which troubleshooting action is NOT acceptable?
A high-pressure switch is a safety control that protects the compressor and system from excessive discharge pressure, so it must not be bypassed to keep the unit running; the cause of the high pressure has to be found and corrected. Inspecting the condenser coil and fan, reading system pressures, and verifying the charge are all normal ways to find that cause.
11. Under 16 TAC §75.100, which work on an air distribution system requires a contractor license under Texas Occupations Code Chapter 1302?
Correct answer: D) System balancing of the air distribution system. The full explanation, with the rule it comes from and why each other option is wrong, is included with Premium access.
12. A load calculation gives a total cooling load of 42,000 Btu/h. Using 12,000 Btu/h per ton, what is the load in tons of cooling?
Correct answer: A) 3.5 tons. The step-by-step working, and the mistake behind each wrong option, are in the full explanation included with Premium access.
13. An R-410A split system has a suction pressure of 118 psig and a suction line temperature of 52°F at the service valve. Use the saturation (dew point) temperature of R-410A at that pressure. What is the system superheat, rounded to the nearest °F?
Correct answer: B) 12°F. The step-by-step working, and the mistake behind each wrong option, are in the full explanation included with Premium access.
14. A mechanical room is 30 ft long, 20 ft wide and 12 ft high. An exhaust fan moves 1,800 CFM. How many air changes per hour does the fan provide?
Correct answer: B) 15 air changes per hour. The step-by-step working, and the mistake behind each wrong option, are in the full explanation included with Premium access.
15. A gas furnace has an input of 100,000 Btu/h and an efficiency of 80 percent. The measured temperature rise is 50°F. Using the 1.08 factor and rounding to the nearest whole CFM, what is the airflow?
Correct answer: C) 1,481 CFM. The step-by-step working, and the mistake behind each wrong option, are in the full explanation included with Premium access.
16. What is the main function of the reversing valve (four-way valve) in a heat pump?
Correct answer: A) Reverses refrigerant flow so the two coils swap evaporator and condenser roles. The full reasoning, and why each other option is wrong, is included with Premium access.
17. At sea level, how is absolute pressure (psia) found from a gauge reading in psig?
Correct answer: D) Add atmospheric pressure of 14.7 psi to the gauge reading. The full reasoning, and why each other option is wrong, is included with Premium access.
18. Lone Star Comfort Systems replaces a 20 in. x 20 in. return grille with a smaller decorative grille on a system that moves the same airflow. The owner now reports a loud whistle at the grille. What is the most likely cause?
Correct answer: A) High face velocity through the smaller free area of the grille. The full reasoning, and why each other option is wrong, is included with Premium access.
19. Which practice is NOT acceptable for a gravity condensate drain line serving an indoor cooling coil?
Correct answer: D) Running part of the line uphill before it reaches the point of disposal. The full reasoning, and why each other option is wrong, is included with Premium access.
20. A condensing unit nameplate lists an MCA of 24 amps and an MOCP of 40 amps. Which statement correctly describes what these two ratings mean?
Correct answer: B) MCA sizes the supply conductors; MOCP is the largest breaker or fuse. The full reasoning, and why each other option is wrong, is included with Premium access.
21. A customer wants to save money by connecting a new gas dryer's exhaust duct to the existing furnace flue instead of cutting a hole in the wall. What should the contractor advise?
Correct answer: B) Run it as a separate duct through an outside wall to the outdoors. The full reasoning, and why each other option is wrong, is included with Premium access.
22. Which technician certification covers a person who works only on low-pressure appliances under 40 CFR 82.161(a)(1)?
Correct answer: A) Type III technician. The full explanation, with the rule it comes from and why each other option is wrong, is included with Premium access.
23. A gas furnace with flame rectification lights normally, but the gas valve closes after about three seconds, and the board retries before locking out. The ignitor, inducer, and pressure switch work correctly. What is the MOST likely cause?
Correct answer: A) A flame sensor that is coated with oxide. The full reasoning, and why each other option is wrong, is included with Premium access.
24. A 10-inch round duct carries 600 CFM. What is the air velocity in the duct, to the nearest 10 fpm?
Correct answer: C) 1,100 fpm. The step-by-step working, and the mistake behind each wrong option, are in the full explanation included with Premium access.
25. Which defrost method melts frost by stopping the compressor and letting above-freezing air in the box warm the coil?
Correct answer: C) Off-cycle (air) defrost. The full reasoning, and why each other option is wrong, is included with Premium access.
26. An electric strip heater element reads 14.4 ohms with the power off. It operates on 240 volts single-phase. Using P = V² / R, how much power does it draw?
Correct answer: D) 4,000 W. The step-by-step working, and the mistake behind each wrong option, are in the full explanation included with Premium access.
27. Which of the following is NOT an appropriate source of combustion air for a gas furnace in a utility room?
Correct answer: B) Air drawn from a bedroom or bathroom that opens into the utility room. The full reasoning, and why each other option is wrong, is included with Premium access.
28. Within how many hours after the work-related death of an employee must an employer report the fatality to OSHA under 29 CFR 1904.39(a)(1)?
Correct answer: A) 8 hours. The full explanation, with the rule it comes from and why each other option is wrong, is included with Premium access.
29. A coil in a humid Gulf Coast home removes 18,000 Btu/h of sensible heat and 12,000 Btu/h of latent heat. What is its sensible heat ratio (SHR)?
Correct answer: B) 0.60. The step-by-step working, and the mistake behind each wrong option, are in the full explanation included with Premium access.
30. Under 29 CFR 1926.1053, how far above the upper landing surface must the side rails of a portable ladder extend when the ladder is used for access?
Correct answer: C) At least 3 feet. The full explanation, with the rule it comes from and why each other option is wrong, is included with Premium access.
31. What does the throw of a supply air outlet describe?
Correct answer: C) The distance the air travels from the outlet before slowing to a set terminal velocity. The full reasoning, and why each other option is wrong, is included with Premium access.
32. A single-phase compressor motor reads 3.6 ohms from C to R and 11.8 ohms from C to S at room temperature. What reading should be expected from S to R?
Correct answer: D) 15.4 ohms. The step-by-step working, and the mistake behind each wrong option, are in the full explanation included with Premium access.
33. Where should a refrigeration machinery room's exhaust system discharge air that may contain escaped refrigerant?
Correct answer: C) To the outdoors, at a point where it cannot re-enter the building. The full reasoning, and why each other option is wrong, is included with Premium access.
34. Lone Star Comfort Systems asks a technician to check the evaporator superheat on a split system with a piston metering device. Which comparison gives this superheat?
Correct answer: C) Suction line temperature compared with the low-side saturation temperature. The full reasoning, and why each other option is wrong, is included with Premium access.
35. Which statement about a liquid receiver in a commercial refrigeration system is INCORRECT?
Correct answer: D) It is placed in the suction line to guard the compressor against liquid. The full reasoning, and why each other option is wrong, is included with Premium access.
36. A company that holds no contractor license offers to adjust the dampers and set the airflow at each register to design values. Under 16 TAC §75.100(f), how is this work classified?
Correct answer: B) System balancing, which requires a Chapter 1302 license. The full explanation, with the rule it comes from and why each other option is wrong, is included with Premium access.
37. An ice maker takes in 250 lb of water per hour at 52 °F, cools it to 32 °F, and freezes all of it into ice at 32 °F. Use 144 Btu/lb for freezing, a specific heat of 1 Btu per lb per °F for water, and 12,000 Btu/h per ton. What refrigeration load is required, in tons to one decimal?
Correct answer: C) 3.4 tons. The step-by-step working, and the mistake behind each wrong option, are in the full explanation included with Premium access.
38. A permit for a replacement system was issued on August 14, 2026, and the crew starts the work on September 21, 2026. Under 16 TAC §75.110(b), may the licensee complete this job under the 2021 code editions?
Correct answer: B) Yes, because the work was permitted before September 1, 2026. The full explanation, with the rule it comes from and why each other option is wrong, is included with Premium access.
39. When a suction line includes a vertical riser, which design condition lets oil return to the compressor?
Correct answer: A) Enough vapor velocity in the riser to sweep the oil upward. The full reasoning, and why each other option is wrong, is included with Premium access.
40. Which practice is INCORRECT when installing a flexible duct run?
Correct answer: D) Compressing extra length into the run to avoid cutting it. The full reasoning, and why each other option is wrong, is included with Premium access.