The PSI subject area Testing: airflow, combustion, electrical and gas. These are original practice notes, not materials of the TDLR or PSI. Texas rules are described from 16 TAC Chapter 75 as in force on January 1, 2027; the technical content uses standard trade formulas. The exam is open book: know where test procedures sit in your references and what to calculate; these notes quote no code values.
1. A furnace delivers 60,000 Btu/h of output into the duct system, and a traverse shows 1,200 CFM. Using the 1.08 factor and rounding to the nearest degree, what is the temperature rise?
Temperature rise = output / (1.08 x CFM) = 60,000 / (1.08 x 1,200) = 46°F. A result of 11°F uses the 4.5 factor, 50°F leaves out the 1.08, and 74°F uses 0.68, the latent heat factor.
2. A technician has confirmed that a gas furnace fires at its nameplate input. The measured temperature rise is 75°F, but the nameplate range is 35°F to 65°F. What is the MOST likely cause?
Temperature rise = output / (1.08 x CFM), so with the input confirmed, a rise above the plate range means too little air is crossing the heat exchanger, as with a dirty filter or blocked return. A blower speed set too high, a larger return grille, or low manifold pressure would all lower the rise, not raise it.
3. A technician must check the manifold gas pressure of a natural gas furnace with a manometer. Where and when should the reading be taken?
Manifold pressure is the gas pressure delivered to the burners, so it is read at the outlet pressure tap of the gas valve while the burners are firing, in inches of water column, and compared with the nameplate value. The inlet tap measures the supply pressure, not the manifold pressure, whether the burners are off or firing, and at the outlet tap with the burners off the valve is closed, so there is no manifold pressure to read.
4. What is external static pressure for a furnace or air handler blower?
External static pressure, measured in in. w.c., is the resistance of the ductwork, grilles, and other components outside the unit cabinet that the blower must overcome. Pressure from air speed is velocity pressure, static plus velocity is total pressure, and the room-to-outdoor difference is building pressure.
5. A combustion analysis of a gas furnace shows carbon monoxide well above the allowable limit. What does this MOST likely indicate?
Elevated CO is a product of incomplete combustion, which can come from flame impingement, a dirty or misadjusted burner, or too little combustion air. Complete combustion produces carbon dioxide and water vapor with little or no CO, so a high CO reading rules it out; temperature rise is an airflow measurement, and a low flue temperature relates to condensation, not to CO production.