What this topic covers
Air Distribution, a subject area of the PSI bulletin for the Texas air conditioning and refrigeration contractor exams: airflow, duct installation, duct sizing, filtration, return and supply grilles, and static pressure. These are original practice notes, not materials of the TDLR or PSI. The Texas rules cited are based on the texts in force on January 1, 2027; the technical content uses standard principles and formulas of the trade. The exam is open book: know where to look in your authorized references and what to calculate, rather than memorizing their values.
Airflow
- Required airflow: CFM = sensible heat (Btu/h) / (1.08 x delta T (°F)). Example: 36,000 / (1.08 x 20) = about 1,670 CFM. Use the room-to-supply difference, not outdoor-to-supply.
- Sensible heat: Btu/h = 1.08 x CFM x delta T; 1.08 x 1,200 x (75 - 57) = about 23,300 Btu/h. Do not swap in the latent constant 0.68 or the total-heat constant 4.5.
- Too little air: drives the coil surface below 32°F, and the coil ices.
- Too much air: warms the coil so less moisture is removed, adds noise at the registers, and can carry condensate into the ducts.
Duct sizing
- Continuity: CFM = velocity (fpm) x area (sq ft); divide square inches by 144.
- Round duct: area = pi x radius squared. A 10 in. duct is 0.545 sq ft, so 600 CFM moves at about 1,100 fpm. Classic errors: diameter used as radius, round duct treated as square.
- Diameter from area: d = square root of (4A / pi); 2,000 CFM at 800 fpm needs 2.5 sq ft (360 sq in.), about a 21 in. duct.
- Equivalent round duct: De = 1.30 x (a x b)^0.625 / (a + b)^0.25; 30 in. x 10 in. gives about 18.3 in. Equal area does not mean equal friction.
- Friction rate: available static x 100 / total effective length. Available static = blower external static minus coil, filter, grille, register and damper losses; total effective length adds fitting lengths to straight duct. Example: 0.80 - (0.22 + 0.10 + 0.03 + 0.05) = 0.40 in. w.c.; 0.40 x 100 / 150 ft = 0.27.
Static pressure
- Total pressure: static + velocity pressure, with velocity pressure = (V / 4005) squared. At 1,800 fpm it is 0.20, so 0.45 static gives 0.65 in. w.c. total.
- External static pressure: resistance of the ducts and devices outside the cabinet that the blower overcomes. Add the magnitudes of supply and return readings: 0.42 + 0.18 = 0.60 in. w.c.
Filtration and grilles
- MERV: higher rating, finer capture and more pressure drop at the same airflow.
- Diagnosis: a higher-MERV filter raises external static, cuts coil airflow, makes supply air colder and can frost the coil; an undercharge frosts a coil but gives warmer supply air.
- Throw: distance until air velocity falls to a set terminal value; drop is the vertical fall, spread the width, induction ratio the share of room air drawn in.
- Face velocity: same CFM through less free area raises velocity, and high face velocity whistles.
Installation and Texas rules
- Leakage and condensation: seal joints with mastic or approved tape; insulation does not stop leaks. A torn vapor barrier lets humid attic air condense on the cold duct.
- Flexible duct: cut to length, fully extended, supported, liner sealed to each collar.
- Balancing: requires a contractor license under Texas Occupations Code Chapter 1302 (16 TAC §75.100(f)(2)); system testing does not (§75.100(f)(1)).
- Duct cleaning: no license only within 16 TAC §75.100(c)(1): supply plenum to supply grilles and return grille to air handler intake, no cutting of ducts or plenums, only grilles removable without cutting or removing other parts.
- Biomedical: testing needs no license (16 TAC §75.100(c)(2)); remediation requires one (§75.100(c)(3)).
- Code in a city: the code the municipality adopted by ordinance (16 TAC §75.100(e)(1)).
Sample questions (5)
1. A cooling load calculation shows a sensible load of 36,000 Btu/h. The return air is 75°F, the supply air is 55°F, and the outdoor design temperature is 95°F. Using sensible heat = 1.08 x CFM x delta-T, what supply airflow is required, to the nearest 10 CFM?
- 400 CFM
- 830 CFM
- 1,670 CFM
- 2,650 CFM
CFM = 36,000 / (1.08 x 20°F) = 1,667, or 1,670 CFM. A result of 400 CFM divides by the total-heat constant 4.5 instead of 1.08; 830 CFM uses the outdoor-to-supply difference of 40°F instead of the room-to-supply temperature difference; 2,650 CFM uses the latent-heat constant 0.68.
2. In a duct system, total pressure at a point is equal to which sum?
- Static pressure plus velocity pressure
- Static pressure minus velocity pressure
- Velocity pressure plus coil pressure drop
- Static pressure plus duct friction loss
Total pressure = static pressure + velocity pressure, where velocity pressure is the pressure of the moving air, VP = (V / 4005)². Subtracting velocity pressure reverses the relationship. A coil pressure drop and the friction loss are resistances the blower overcomes, not components of the total pressure at a point.
3. A duct system is sized by the equal-friction method. The blower is rated for 0.80 in. w.c. of external static pressure at design airflow, and the coil, filter, supply grilles, and return grille all draw from it. Their pressure drops are 0.22, 0.10, 0.03, and 0.05 in. w.c. The longest run has 80 ft of straight duct plus fittings equivalent to 70 ft. What friction rate should be used to size the ducts, to the nearest 0.01 in. w.c. per 100 ft?
- 0.27 in. w.c./100 ft
- 0.50 in. w.c./100 ft
- 0.53 in. w.c./100 ft
- 1.00 in. w.c./100 ft
Available static = 0.80 - (0.22 + 0.10 + 0.03 + 0.05) = 0.40 in. w.c.; total effective length = 80 + 70 = 150 ft; friction rate = 0.40 x 100 / 150 = 0.27. A result of 0.50 uses only the 80 ft of straight duct, 0.53 forgets to deduct the component losses, and 1.00 makes both mistakes.
4. A company that holds no contractor license under Texas Occupations Code Chapter 1302 wants to offer duct services. Under 16 TAC §75.100(c), which statement is correct?
- It may perform biomedical remediation but not biomedical testing
- It may perform biomedical testing but not biomedical remediation
- It may perform neither biomedical testing nor biomedical remediation
- It may perform both biomedical testing and biomedical remediation
16 TAC §75.100(c)(2) allows biomedical testing without a contractor license, while §75.100(c)(3) says biomedical remediation requires a contractor license under Chapter 1302. The reverse split is backward, and the options that allow both or neither each ignore one of the two paragraphs.
5. A 3-ton system delivers 1,200 CFM. The return air is 75°F, the supply air is 57°F, and the outdoor air is 95°F. Using sensible heat = 1.08 x CFM x delta-T, how much sensible cooling does the air stream provide, to the nearest 100 Btu/h?
- 14,700 Btu/h
- 23,300 Btu/h
- 49,200 Btu/h
- 97,200 Btu/h
Q = 1.08 x 1,200 x (75 - 57) = 23,328, or 23,300 Btu/h. A result of 14,700 uses the latent constant 0.68; 49,200 uses the outdoor-to-supply difference of 38°F; 97,200 uses the total-heat constant 4.5.