What this topic covers
HVACR Systems in the PSI bulletin: components, installation and refrigeration systems. These are original practice notes, not materials of the TDLR or PSI. License scope and installation limits come from Texas Occupations Code ch. 1302 and 16 TAC ch. 75, and the federal rule from 40 CFR part 84, as in force on January 1, 2027; the system content uses standard principles of the trade. The exam is open book: know where each definition and limit sits in your authorized references and what to add up before comparing.
Types of work and license class
- Environmental air conditioning: human comfort (Texas Occupations Code §1302.002(11)).
- Commercial refrigeration: temperature or humidity for the intended use of a specific space, such as product storage (§1302.002(6)).
- Process cooling or heating: solely for production requirements or the proper operation of equipment (§1302.002(15)); it excludes cryogenic work (16 TAC §75.100(d)(1)).
- Class B: not more than 25 tons cooling and 1.5 million Btu/h output heating (§1302.253(c)), with no exception for replacement. A Class A license covers any size (§1302.253(b)). Example: 156,000 + 108,000 = 264,000 Btu/h; 264,000 / 12,000 = 22.0 tons, within Class B.
- Endorsement: sets the type of work, not its size; no contracting in a type not endorsed (§1302.254(d)). A technician's certification adds no endorsement.
Installation limits (16 TAC §75.100)
- Electrical: on new construction, connect the appliance to the line or disconnect provided for that purpose, not a new branch circuit or larger breaker (§75.100(a)(1)); replacement work is in (a)(2).
- Control wiring: 50 volts or less; with the commercial refrigeration endorsement, commercial refrigeration control wiring of any voltage on the equipment side of the disconnect (§75.100(a)(3)).
- Fuel gas piping: only between the appliance and the existing piping system, connected at an existing shut-off valve; existing piping, stops and shut-off valves shall not be altered (§75.100(b)(1)).
Heat pump components
- Reversing valve: switches the discharge and suction connections so each coil changes duty; not the liquid line. Whether it is energized in cooling or heating depends on the manufacturer.
- Check valve: in parallel with each TXV, it opens when liquid flows away from its coil; in cooling, the one around the outdoor TXV passes liquid to the indoor TXV.
- Accumulator vs receiver: the accumulator in the suction line catches liquid that would slug the compressor; the receiver in the liquid line after the condenser stores charge. An oil separator sits in the discharge line.
Commercial refrigeration controls
- EPR: at the warmer evaporator outlet, holds its minimum evaporator pressure above the common suction pressure.
- CPR: in the suction line near the compressor, throttles when suction pressure is too high after defrost or startup.
- Head-pressure control: in low ambient, backs liquid into the condenser to raise condensing pressure; it needs a receiver large enough for the displaced charge.
Defrost and ice machines
- Off-cycle defrost: box air above 32 °F melts the frost (medium temperature); air at 0 °F cannot, so low-temperature coils use electric heaters or hot gas.
- Ice harvest: the hot gas solenoid valve sends discharge vapor through the evaporator so the ice releases.
- HFC limit: 40 CFR 84.54(a)(4) restricts a GWP of 150 or greater for retail food stand-alone units (700 for products in (a)(1)); in force on January 1, 2027, under federal review.
Sample questions (5)
1. Under 16 TAC §75.100(a)(1), which electrical task may a licensee perform on new construction of an environmental air conditioning system?
- Install a new branch circuit from the service panel to the appliance location
- Replace the panel breaker with one of a higher amperage rating for the unit
- Extend the utility service conductors to the meter base serving the building
- Connect the appliance to the electrical line or disconnect provided for it
16 TAC §75.100(a)(1) allows a licensee, on new construction, to connect the appliance to the electrical line or disconnect that is provided for that purpose. The rule grants only that connection: a new branch circuit, a higher-amperage breaker, and utility service conductors are not named in it. Replacement work is handled separately in §75.100(a)(2).
2. Lone Star Cold Storage Services holds a Class B license with a commercial refrigeration and process cooling or heating endorsement. Its crew installs 120-volt control wiring for the evaporator fan relays of a walk-in cooler, entirely on the equipment side of the disconnect. Under 16 TAC §75.100(a)(3), is this work permitted?
- Yes; commercial refrigeration control wiring of any voltage is allowed on the equipment side of the disconnect
- No; the rule limits licensees to control wiring of 50 volts or less on commercial refrigeration equipment
- No; control wiring above 50 volts requires the environmental air conditioning endorsement on the license
- Yes; but the wiring must be installed on the line side of the disconnect that serves the walk-in cooler
16 TAC §75.100(a)(3) lets a licensee install control wiring of 50 volts or less, and lets a licensee with the commercial refrigeration endorsement install commercial refrigeration control wiring of any voltage as long as it is on the equipment side of the disconnect. The 50-volt limit therefore does not cap this job. The environmental air conditioning endorsement is not the one that governs commercial refrigeration wiring, and the line side of the disconnect is outside the allowance.
3. Under 16 TAC §75.100(b)(1), fuel gas piping installed by a licensee for a new or replaced system is limited to the piping between which two points?
- The gas meter and the first shut-off valve located upstream of the appliance
- The appliance and the existing piping system, at an existing shut-off valve
- The utility service line and the existing piping system inside the building
- The appliance and the gas meter, including any shut-off valve changes needed
16 TAC §75.100(b)(1) limits a licensee's fuel gas piping to the portion between the appliance and the existing piping system, connected at an existing shut-off valve provided for such use. Work that starts at the meter or the utility service line goes beyond that portion. The same paragraph says existing piping systems, stops, and shut-off valves shall not be altered by a licensee.
4. A licensee is replacing a gas furnace and needs new fuel gas piping. Which action is NOT allowed under 16 TAC §75.100(b)(1)?
- Installing piping between the furnace and an existing shut-off valve
- Connecting the new piping at an existing shut-off valve provided for the purpose
- Altering an existing shut-off valve so that the new piping run is shorter
- Replacing the old furnace piping downstream of the existing shut-off valve
16 TAC §75.100(b)(1) says existing piping systems, stops, or shut-off valves shall not be altered by a licensee, so changing a valve to shorten the run is not allowed. The other three actions are permitted: fuel gas piping for a new or replaced system may be installed by a licensee, limited to the portion between the appliance and the existing piping system and connected at an existing shut-off valve, so replacing the old piping downstream of that valve is within the limit.
5. A heat pump has a TXV at the indoor coil and another TXV at the outdoor coil. In the cooling mode, how does liquid leaving the outdoor coil reach the indoor TXV without passing through the outdoor TXV?
- Through a check valve piped around the outdoor TXV, open in that direction
- Through the reversing valve, which reroutes the liquid line around the TXV
- Through the suction accumulator, which sends the liquid to the indoor coil
- Through the TXV external equalizer line, which carries liquid past it
When each coil of a heat pump has its own TXV, a check valve is piped in parallel with each TXV: it opens when liquid flows away from its coil and closes in the other mode so that the TXV meters. In cooling, the check valve around the outdoor TXV passes the liquid on to the indoor TXV. The reversing valve switches only the compressor discharge and suction vapor connections, not the liquid line; the accumulator sits in the suction line to protect the compressor from liquid; and the external equalizer line only senses evaporator outlet pressure for the TXV, so it carries no liquid flow.