What this topic covers
The PSI subject area Piping: condensate, pipe fittings, pipe sizing, pipe type, support and valves. These are original practice notes, not materials of the TDLR or PSI. The Texas rule is described from 16 TAC Chapter 75 as in force on January 1, 2027; the technical content uses standard trade principles and formulas. The exam is open book: know where slope, sizing and support requirements sit in your mechanical and plumbing code references and what to calculate; these notes quote no code values.
Condensate
- Gravity drain: water moves downhill only; a section that rises holds water back until the pan overflows. Use a continuous downward slope, supports that prevent sags, and a way to clear a blockage without cutting the pipe. Minimum slope and pipe size come from the applicable code.
- Draw-through unit: the pan is under negative pressure, so an untrapped drain pulls air up and holds water in the pan; a properly sized trap fixes this. A float switch only shuts the equipment off.
- Texas rule: drain piping terminating outside the building must be installed by a licensee; if it terminates inside, a licensee may make the connection on the inlet side of a properly installed trap, following the plumbing and building codes (16 TAC §75.100(b)(2)).
Pipe type
- ACR tube: named by its actual outside diameter and supplied cleaned and capped to keep out moisture and debris.
- Water-type tube: uses a nominal size, with an outside diameter 1/8 in. larger than the stated size.
- Types K, L, M: for the same nominal size, K has the thickest wall, L is thinner, M is the thinnest; the color stripe identifies the type.
Fittings and joining
- Swaged joint: one tube end is expanded so a same-size tube fits inside, then the overlap is brazed.
- Other joints: a flare is a nut-and-seat mechanical connection, a press fitting uses a crimped sealing ring, a threaded fitting relies on sealant.
- Brazing with nitrogen: a low flow of dry nitrogen displaces air and prevents copper oxide scale that can plug a strainer or metering device. Never use compressed air or oxygen to purge or test: both promote oxidation and add a fire hazard with oil present.
Pipe sizing
- Suction risers: oil moves up only when vapor velocity is high enough, so risers are sized for oil return, often with a trap at the bottom.
- Part load: a riser sized for full load may be too slow at part load; oil collects in the line and the crankcase level drops. Remedies: a smaller riser or a double riser.
- Pressure drop: total equivalent length = straight tube + (number of each fitting or valve x its equivalent length); drop = equivalent length / 100 x friction rate per 100 ft. Example: 60 ft + 8 fittings at 2.5 ft + 2 valves at 6.0 ft = 92 ft; at 2.0 psi per 100 ft the drop is 1.8 psi.
Support and vibration
- Near the compressor: a rigid clamp close to a vibrating compressor makes the tube flex until the copper fatigues and cracks; use a vibration loop or offset and supports that isolate the tube.
Valves
- King valve: the liquid-line service valve at the receiver outlet; closing it isolates stored liquid for pump-down.
- Others: the suction service valve is at the compressor inlet, the discharge check valve at the compressor outlet, and the liquid-line solenoid valve controls flow to the metering device.
Sample questions (5)
1. Which statement correctly describes how copper tube made for air conditioning and refrigeration (ACR tube) is sized?
- By its actual outside diameter, and it is supplied cleaned and capped
- By its nominal inside diameter, the same way as plumbing water tube
- By a nominal size that is 1/8 in. smaller than its outside diameter
- By its wall-thickness gauge number, with the outside diameter variable
ACR tube is identified by its actual outside diameter (a 3/4 in. tube measures 3/4 in. across the outside) and is supplied cleaned and capped to keep moisture and debris out. Water-type copper tube uses a nominal size, with an outside diameter 1/8 in. larger than the stated size, so the sizing systems differ. Neither inside diameter nor a gauge number identifies ACR tube.
2. In refrigerant piping, what is a swaged joint?
- A flared tube end held by a nut against a 45-degree fitting seat
- A tube end expanded so a same-size tube slips inside before brazing
- A press fitting with a sealing ring that is crimped onto both tubes
- A threaded fitting made up with a sealant on the male thread
A swaged joint is formed by expanding the end of one tube with a swaging tool so a tube of the same size fits inside it, and the overlap is then brazed. A flared joint is a nut-and-seat mechanical connection, a press fitting uses a crimped sealing ring, and a threaded fitting relies on sealant; none of these is formed by expanding one tube end to accept another.
3. What is the correct practice while brazing joints in a copper refrigerant line?
- Flow compressed air through the tube at a low regulated pressure
- Flow a small amount of oxygen through the tube to burn off oil
- Flow dry nitrogen through the tube at a low regulated pressure
- Seal both ends of the tube so that no gas moves inside it
Dry nitrogen is inert, so a low flow displaces the air and keeps copper oxide scale from forming inside the tube; scale can later plug a strainer or metering device. Compressed air and oxygen both contain oxygen, which promotes oxidation and adds a fire hazard when oil is present. A sealed tube builds pressure from the heat and still contains air.
4. Which statement about the wall thickness of copper tube Types K, L, and M of the same nominal size is correct?
- Type M has the thickest wall, followed by Type L and then Type K
- Type L has the thickest wall, followed by Type K and then Type M
- The three types share one wall thickness and differ just in stripe color
- Type K has the thickest wall, followed by Type L and then Type M
For the same nominal size, Type K has the thickest wall, Type L is thinner, and Type M is the thinnest; the color stripe on the tube identifies the type because the walls really do differ. The order M, L, K reverses the real order, the order L, K, M wrongly puts Type L ahead of Type K, and the three types do not share one wall thickness.
5. In a commercial refrigeration system, what is the king valve?
- The suction service valve at the compressor inlet
- The liquid-line service valve at the outlet of the receiver
- The check valve at the compressor discharge outlet
- The solenoid valve ahead of the evaporator metering device
The king valve is the liquid-line service valve at the receiver outlet; closing it isolates the stored liquid so the system can be pumped down. The suction service valve sits at the compressor inlet, the discharge check valve sits at the compressor outlet, and the liquid-line solenoid valve controls flow to the metering device rather than isolating the receiver.