The Refrigeration Principles subject area of the PSI bulletin: heat transfer, physics and system pressure. These are original practice notes, not materials of the TDLR or PSI. The technical content uses standard principles and formulas of the trade; the federal refrigerant rule mentioned below is described from 40 CFR 84 as in force on January 1, 2027. The exam is open book: know where to look in your allowed references and what to calculate, rather than memorizing values; saturation data needed in a problem is given in it.
1. A technician explains sensible and latent heat to an apprentice. Which statement correctly describes latent heat?
Latent heat is the heat absorbed or released while a substance changes state, such as boiling or condensing, with no temperature change. Heat that raises the temperature without a change of state, and that a thermometer can measure, is sensible heat. Heat moving between substances in direct contact is conduction, which describes how heat travels rather than the type of heat.
2. Under 40 CFR 84.54(a)(1), effective January 1, 2025, no person may manufacture or import self-contained residential and light commercial air conditioning and heat pump products that use a regulated substance with a global warming potential (GWP) at or above which value?
40 CFR 84.54(a)(1) sets a GWP of 700 or greater for self-contained residential and light commercial air conditioning and heat pump products, effective January 1, 2025. The 150 threshold applies to household refrigerators and freezers, stand-alone retail food refrigeration units, and vending machines under 84.54(a)(3) through (a)(5). Neither 400 nor 1,500 is a threshold for this product category. 40 CFR 84 is a gray-zone rule under federal review; confirm the current text.
3. A technician must add refrigerant from a cylinder of a zeotropic blend such as R-407C, which has temperature glide, to a system that is low on charge. How should the refrigerant leave the cylinder?
The components of a zeotropic blend boil at different temperatures, which causes the glide. Drawing vapor from the cylinder removes the more volatile components first and shifts the composition of what is left, so the blend is removed from the cylinder as liquid and metered into the system so that liquid does not reach the compressor. Heating the cylinder or feeding a vapor and liquid mixture does not keep the composition constant.
4. In an evaporator coil, room air blows across the fins and the heat then passes into the refrigerant inside the tubes. Which pair of methods describes this heat path?
Moving air carries heat to the fin surface by convection. The heat then travels through the solid metal of the fins and tube wall by conduction, flowing from the warmer air toward the colder refrigerant. Radiation is a minor effect at these small temperature differences and does not carry heat through a solid tube wall, and heat delivered by moving air is convection, not conduction.
5. Which statement about compression ratio is NOT correct?
Compression ratio is absolute discharge pressure divided by absolute suction pressure, so both gauge readings must first be converted with psia = psig + 14.7; dividing the psig readings directly gives a wrong, higher value. The other statements are correct: the ratio compares absolute pressures, it rises when suction pressure drops while head pressure stays the same, and a higher ratio raises the discharge temperature and lowers the volumetric efficiency and capacity of the compressor.