Service in the PSI bulletin: electrical checks, diagnostics, refrigerant recovery, superheat and subcooling. These are original practice notes, not materials of the TDLR or PSI. Recovery, certification and leak repair are described from 40 CFR part 82, subpart F, and part 84, subpart C, as in force on January 1, 2027; the service content uses standard formulas of the trade. The exam is open book: know which pressure to convert to a saturation temperature and where the recovery tables sit, then calculate.
1. Assume 1 in. Hg equals 25,400 microns. During evacuation, a vacuum gauge reads 0.02 in. Hg absolute. What is that pressure in microns?
Microns = in. Hg x 25,400 = 0.02 x 25,400 = 508 microns. A decimal slip (0.2 in. Hg) gives 5,080, quoting the conversion factor without multiplying gives 25,400, and dividing 25,400 by 0.02 gives 1,270,000.
2. Under 40 CFR 82.154(a)(1), which of the following is NOT exempt from the venting prohibition?
40 CFR 82.154(a)(1) exempts carbon dioxide in any application, ammonia in absorption units, and propane (R-290) in household refrigerators, among the listed substitutes and end-uses. R-410A in residential air conditioning is not on that list, so it is a non-exempt substitute and knowingly venting it is prohibited; under 40 CFR 82.154(a)(2), only de minimis releases that occur while the practices of §§82.155 and 82.156 are observed fall outside the prohibition.
3. A technician checks a hermetic compressor with an ohmmeter. With one probe on the S terminal and the other on bare metal of the compressor shell, the meter reads 12 ohms. What does this reading indicate?
Between any terminal and the shell, the meter should read open (OL); a measurable reading such as 12 ohms means the winding insulation has failed and the winding is grounded. An open winding shows infinite resistance between terminals, a normal start winding is measured terminal to terminal rather than to the shell, and a capacitor is not in this test path.
4. Under Table 1 of 40 CFR 82.156(a), to what level must a medium-pressure appliance with a full charge of 200 pounds or more be evacuated, using recovery equipment made on or after November 15, 1993?
Table 1 of 40 CFR 82.156(a) requires 15 inches of mercury vacuum for a medium-pressure appliance with a full charge of 200 pounds or more when the recovery equipment was made on or after November 15, 1993. 10 inches applies to a medium-pressure appliance under 200 pounds, 4 inches is the level for recovery equipment made before November 15, 1993, and 0 inches applies to very high-pressure appliances and to high-pressure appliances under 200 pounds.
5. A 75-pound comfort-cooling chiller is charged with R-22. Under 40 CFR 82.157(c)(2), above what leak rate must the owner repair the appliance?
40 CFR 82.157(c)(2)(iii) sets a 10 percent leak rate for comfort cooling appliances and other appliances with a full charge of 50 or more pounds not covered by (c)(2)(i) or (ii); §82.157 applies because the chiller holds 50 or more pounds of R-22, a class II refrigerant. 20 percent is the commercial refrigeration rate and 30 percent is the industrial process refrigeration rate. 15 percent was the comfort-cooling rate of the former 40 CFR 82.156(i), which is outdated: since January 1, 2019, §82.157 applies in lieu of it.