What this topic covers

Basic Refrigeration Components in the PSI bulletin: compressors, condensers, evaporators, metering devices and refrigerants. These are original practice notes, not materials of the TDLR or PSI. The federal refrigerant rules are described from 40 CFR part 82, subpart F, as in force on January 1, 2027; the component content uses standard principles and formulas of the trade. The exam is open book: know where the refrigerant definitions sit in your authorized references and which readings to compare for each check.

Compressors

Condensers and evaporators

Metering devices

Refrigerants and EPA rules

Take the free test · full question bank and mock exams with a subscription

Sample questions (5)

1. A technician explains that a reciprocating compressor failed because of slugging. What does slugging describe?

  1. Hot discharge vapor flowing back to the suction side after shutdown
  2. Refrigerant vapor leaking past the piston rings during compression
  3. Excess oil being carried out of the crankcase along with the discharge gas
  4. Liquid refrigerant reaching the compression chamber with suction vapor

Slugging is liquid refrigerant (or oil) reaching the compression chamber with the suction vapor, often as a result of liquid floodback through the suction line. Liquid cannot be compressed, so valves, rods, and pistons can break. Vapor leaking past the piston rings is blow-by, which cuts capacity but is not slugging. Hot discharge vapor flowing back to the suction side after shutdown points to a leaking discharge valve, and oil carried out with the discharge gas is oil loss, not slugging.

2. Compared with a fully hermetic compressor, which feature belongs to a semi-hermetic compressor?

  1. Its motor windings are cooled by water instead of refrigerant vapor
  2. Its shell is welded closed so the internal parts cannot be inspected
  3. Its motor sits outside the refrigerant circuit behind a shaft seal
  4. Its bolted housing allows field repair of valves and internal parts

A semi-hermetic compressor keeps the motor and compressor in a housing with a bolted cover, so valve plates, pistons, and the motor can be serviced in the field. A fully hermetic compressor is welded shut and is replaced as a unit. An open-drive compressor has its motor outside the refrigerant circuit and a shaft seal. Semi-hermetic motors are normally cooled by returning suction vapor, not by water.

3. What happens to the refrigerant in the first section of a condenser coil, called the desuperheating zone?

  1. Superheated vapor is cooled down to its saturation temperature
  2. Saturated liquid is cooled further below its saturation temperature
  3. Saturated vapor condenses to liquid at a constant temperature
  4. Liquid refrigerant flashes into vapor as its pressure drops

In the desuperheating zone the hot discharge vapor gives up sensible heat until it reaches its saturation temperature. Cooling saturated liquid below saturation is the subcooling zone at the end of the coil. Condensing at a constant temperature is the middle zone. Flashing into vapor as pressure drops happens at the metering device, not in the condenser.

4. As the load on an evaporator changes, what does a thermostatic expansion valve (TXV) try to hold nearly constant?

  1. The evaporator pressure at the valve outlet
  2. The refrigerant flow rate through the valve
  3. The superheat of vapor at the evaporator outlet
  4. The subcooling of liquid at the condenser outlet

A TXV compares the temperature sensed by its bulb on the suction line with the evaporator pressure and opens or closes to keep the superheat at the evaporator outlet nearly constant as the load changes. Holding a constant evaporator pressure is how an automatic (constant-pressure) expansion valve works. The flow rate through a TXV rises and falls with the load, so it is not held constant. Subcooling at the condenser outlet is a high-side value that the TXV does not control.

5. Under 40 CFR 82.152, which description fits a high-pressure appliance?

  1. A liquid phase saturation pressure below 45 psia at 104 °F
  2. A liquid phase saturation pressure between 170 psia and 355 psia at 104 °F
  3. A liquid phase saturation pressure between 45 psia and 170 psia at 104 °F
  4. A liquid phase saturation pressure above 355 psia at 104 °F

40 CFR 82.152 defines a high-pressure appliance as one using a refrigerant with a “liquid phase saturation pressure between 170 psia and 355 psia at 104 °F”. Below 45 psia describes a low-pressure appliance, 45 psia to 170 psia a medium-pressure appliance, and above 355 psia a very high-pressure appliance.