Equipment Requirements and Design, a subject area of the PSI bulletin for the Texas air conditioning and refrigeration contractor exams: sensible and latent capacities, heat loads, HVACR codes and voltage, plus efficiency ratings. These are original practice notes, not materials of the TDLR or PSI. Texas law and rules and federal regulations are described from the texts in force on January 1, 2027; the technical content uses standard principles and formulas of the trade. The exam is open book: know where to look in your authorized references and what to calculate, rather than memorizing their values.
1. A supply fan moves 1,200 CFM across a cooling coil. Return air enters at 78°F and supply air leaves at 55°F. Using sensible heat = 1.08 x CFM x delta T, what sensible capacity is delivered to the air?
Sensible heat = 1.08 x CFM x delta T = 1.08 x 1,200 x (78 - 55) = 29,808 Btu/h. 18,768 Btu/h wrongly uses the 0.68 latent factor; 71,280 Btu/h uses the 55°F supply temperature instead of the 23°F difference; 124,200 Btu/h uses the 4.5 total-heat factor, which needs an enthalpy change in Btu/lb, not delta T.
2. Coil airflow is 800 CFM. Entering air is 78°F and leaving air is 56°F (delta T 22°F), and the humidity ratio drops by 36 grains of moisture per lb of dry air. Using latent heat = 0.68 x CFM x grain difference, what latent capacity does the coil remove?
Latent heat = 0.68 x CFM x grain difference = 0.68 x 800 x 36 = 19,584 Btu/h. 19,008 Btu/h is the sensible load (1.08 x 800 x 22); 11,968 Btu/h puts the 22°F temperature drop into the latent formula; 31,104 Btu/h applies the 1.08 sensible factor to the grains difference.
3. An insulated wall has 600 ft² of net area and an assembly R-value of 15 (hr·ft²·°F/Btu). The indoor design temperature is 75°F and the outdoor design temperature is 105°F. Using Q = U x A x delta T with U = 1/R, what is the conduction heat gain through the wall?
U = 1/15, so Q = 600 x 30 / 15 = 1,200 Btu/h. 40 Btu/h leaves out delta T (600 / 15); 300 Btu/h computes A x R / delta T; 270,000 Btu/h multiplies by R as if R were U.
4. A three-phase compressor motor on a 208-volt supply draws 20 amps per line at a power factor of 0.90. Using P = 1.732 x V x I x PF, how much real power does the motor draw?
P = 1.732 x 208 x 20 x 0.90 = 6,485 W. 3,744 W leaves out the 1.732 (square root of 3) factor; 4,160 W also drops the power factor (208 x 20); 2,160 W applies the single-phase formula to the 120-volt line-to-neutral value (120 x 20 x 0.90).
5. A technician measures line voltages of 452, 464, and 468 volts on a nominal 460-volt three-phase compressor supply. Using percent imbalance = maximum deviation from the average / average x 100, what is the voltage imbalance?
The average is 461.3 V and the largest deviation is 9.3 V (the 452 V leg), so 9.3 / 461.3 x 100 = 2.0%. 0.3% compares the average with the 460 V nameplate; 1.7% measures the deviation from 460 V instead of from the average; 3.5% divides the 16 V spread between the high and low readings by the average.