What this topic covers

The Controls subject area of the PSI bulletin: general controls, pressure and safety controls, and temperature controls. These are original practice notes, not materials of the TDLR or PSI. The Texas rule on control wiring is described from 16 TAC Chapter 75 as in force on January 1, 2027; the technical content uses standard principles of the trade. The exam is open book: know where to look in your allowed references and what to calculate, rather than memorizing values.

General controls

Forced-air furnace sequence (described in words)

Pressure and safety controls

Temperature controls and defrost

Texas rule on control wiring

Take the free test · full question bank and mock exams with a subscription

Sample questions (5)

1. A gas furnace with an induced-draft inducer receives a call for heat. The inducer runs, but the ignitor never glows and the gas valve never opens. Assume the limit and rollout switches are closed. What is the MOST likely cause?

  1. A flame sensor that is coated with oxide deposits
  2. A 24-volt control transformer that has failed open
  3. A blower relay that fails to energize on the call
  4. An inducer pressure switch that has failed and stays open

On a call for heat, the control board waits for the inducer pressure switch to close and prove draft before it energizes the ignitor and gas valve, so a switch that stays open stops the sequence after the inducer starts. A coated flame sensor matters only after ignition, a failed 24-volt transformer would prevent the call for heat and the inducer start, and the blower relay is not part of the pre-ignition path.

2. A control transformer has a 120-volt primary and a 24-volt secondary and is rated 40 VA. Rounding to two decimal places, what is the maximum current the secondary can supply?

  1. 0.33 A
  2. 0.60 A
  3. 1.67 A
  4. 5.00 A

Current = VA / volts = 40 VA / 24 V = 1.67 A on the secondary. A result of 0.33 A divides by the 120-volt primary voltage, which gives the primary current instead, 0.60 A inverts the ratio (24 / 40), and 5.00 A divides the primary voltage by the secondary voltage (120 / 24).

3. What is the function of a contactor in a compressor control circuit?

  1. It uses a low-voltage coil to close heavy contacts that switch compressor power
  2. It reduces line voltage to 24 volts for the thermostat circuit and control coils
  3. It stores energy in the run circuit to give the motor extra starting torque
  4. It senses discharge pressure and opens the control circuit on high pressure

A contactor is a relay-type switch in which a small control coil, usually 24 volts, closes heavier contacts that carry the compressor line-voltage current. Reducing voltage to 24 volts is the job of a control transformer, storing energy for torque is the job of a capacitor, and sensing discharge pressure is the job of a high-pressure switch.

4. Under 16 TAC §75.100(a)(3), apart from the commercial refrigeration endorsement exception, a licensee may install and service control wiring of how many volts or less?

  1. 24 volts or less
  2. 50 volts or less
  3. 120 volts or less
  4. 240 volts or less

16 TAC §75.100(a)(3) allows a licensee to install and service control wiring of 50 volts or less; any voltage is allowed only for commercial refrigeration control wiring on the equipment side of its disconnect, by a licensee with that endorsement. A 24-volt limit confuses the rule with the usual thermostat-circuit voltage, and 120 and 240 volts are line voltages for equipment power, outside the general control-wiring allowance.

5. Under 16 TAC §75.100(a)(3), which statement about control wiring on a walk-in cooler is correct for a licensee who holds the commercial refrigeration endorsement?

  1. Wiring of any voltage may be installed on the line side of the disconnect serving it
  2. Wiring is limited to 50 volts or less, exactly as it is for other equipment
  3. Wiring up to 120 volts may be installed on either side of the disconnect it serves
  4. Wiring of any voltage may be installed on the equipment side of the disconnect

16 TAC §75.100(a)(3) lets a licensee with the commercial refrigeration endorsement install control wiring of any voltage, provided the wiring is on the equipment side of the disconnect installed for that purpose. The 50-volt limit applies to control wiring generally, not to endorsed commercial refrigeration work; line-side wiring is not covered; and the rule contains no 120-volt limit or either-side allowance.