What this topic covers
Ventilation, a subject area of the PSI bulletin for the Texas air conditioning and refrigeration contractor exams: air equipment and the machinery room. These are original practice notes, not materials of the TDLR or PSI. The Texas rule cited is based on the text in force on January 1, 2027; the technical content uses standard principles and formulas of the trade. Ventilation questions lean on the mechanical codes and on ASHRAE standards, and the exam is open book: know where to look in your authorized references and what to calculate, rather than memorizing their values. Only settled principles are summarized here, without code figures.
Make-up air and building pressure
- Make-up air: outdoor air deliberately supplied to replace the air that exhaust fans or hoods remove, so the building does not go under negative pressure.
- Not make-up air: recirculated air does not replace exhausted air, and uncontrolled leakage into the building is infiltration.
- Negative pressure: when hoods remove more air than the building replaces (for example 1,200 CFM more), doors become hard to open and backdrafting occurs.
- Correct fix: supply make-up air to remove the deficit. Speeding up the hood fan makes it worse, and closing return grilles adds no air.
Air changes and airflow
- Room volume: length x width x height, in cubic feet. Use the volume, not the floor area.
- Air changes per hour: ACH = CFM x 60 / volume. A 30 ft x 20 ft x 12 ft room (7,200 cu ft) with 1,800 CFM gets 1,800 x 60 / 7,200 = 15 ACH. Leaving out the 60 gives air changes per minute.
- Required airflow: CFM = volume x ACH / 60. A 25 ft x 16 ft x 10 ft room (4,000 cu ft) at an assumed 12 air changes per hour needs 4,000 x 12 / 60 = 800 CFM. Without the division by 60 the result is in cubic feet per hour.
- Exam habit: when a required rate depends on a code, the question states it as an assumption; apply the formula to the stated figure.
Machinery room
- Purpose: isolates refrigeration equipment and its refrigerant from occupied space.
- Characteristic safeguards: refrigerant leak detection and a dedicated exhaust that removes escaped refrigerant, the approach of ASHRAE 15.
- Wrong designs: tying the room to the air handler, sealing it with no exhaust, or letting the vapor mix with office air spreads or traps refrigerant instead of removing it.
Machinery room exhaust
- What it does: removes equipment heat, dilutes escaped refrigerant vapor and moves it outdoors. It does not supply conditioned air to other floors; that is the air distribution system.
- Where it discharges: outdoors, away from openings and intakes where the refrigerant could return. A corridor, a return-air plenum or an attic is inside the building and would spread the refrigerant.
Standards referenced in Texas
- ASHRAE 15: the safety standard for refrigeration systems and their machinery rooms. 16 TAC §75.110(c) changes references to ASHRAE 15-2022 so they refer to ASHRAE 15-2024.
- ASHRAE 34: a different standard, for refrigerant designation and safety classification; 16 TAC §75.110(c) separately changes references to 34-2022 into 34-2024.
Sample questions (5)
1. Under 16 TAC §75.110(c), references to ASHRAE 15-2022 in the adopted codes are modified to refer to which standard?
- ASHRAE 15-2019
- ASHRAE 34-2022
- ASHRAE 34-2024
- ASHRAE 15-2024
16 TAC §75.110(c) modifies references to ASHRAE 15-2022 so that they refer to ASHRAE 15-2024, the safety standard for refrigeration systems and their machinery rooms. ASHRAE 15-2019 is an older edition that the rule does not name. ASHRAE 34 is a different standard, for refrigerant designation and safety classification: the rule separately changes references to 34-2022 into 34-2024, so neither 34-2022 nor 34-2024 replaces 15-2022.
2. In ventilation terminology, what is make-up air?
- Outdoor air supplied to replace the air removed by exhaust fans or hoods
- Recirculated return air that is filtered and sent back into the same room
- Air that leaks into a building through the ceiling when the doors are closed
- Conditioned supply air that is mixed with refrigerant to detect small leaks
Make-up air is outdoor air deliberately supplied to replace air that exhaust fans or hoods remove, which keeps the building from going under negative pressure. Recirculated air does not replace exhausted air, uncontrolled leakage is infiltration, and mixing refrigerant into supply air is not a ventilation practice.
3. Which safeguard is characteristic of a refrigeration machinery room?
- A return-air opening that ties the room to the building's air handler duct
- A refrigerant leak detector that triggers a dedicated mechanical exhaust system
- A sealed room with no exhaust so escaped refrigerant stays out of the building
- A recirculating fan that mixes escaped refrigerant with air from nearby offices
A machinery room isolates the equipment and its refrigerant from occupied space, and its characteristic safeguards are leak detection and a dedicated exhaust that removes escaped refrigerant (the approach of ASHRAE 15). Tying the room to the air handler, sealing it with no exhaust, or mixing the vapor with office air would each spread or trap refrigerant instead of removing it.
4. A restaurant's kitchen hoods exhaust 3,000 CFM, but the building's outdoor air system supplies only 1,800 CFM. Doors are hard to open and gas equipment backdrafts. What correction addresses the cause?
- Raise the hood fan speed so more air is pulled out of the kitchen
- Close the return-air grilles in the kitchen to hold conditioned air in
- Replace the outdoor air with recirculated return air from the dining room
- Add make-up air to replace the exhausted air that is not being supplied
The hoods remove 1,200 CFM more than the building replaces, so the building is under negative pressure, which makes doors hard to open and causes backdrafting. Adding make-up air removes that deficit. Speeding up the hood fan makes it worse, closing return grilles does not add air, and recirculated air does not replace exhausted air.
5. Which of the following is NOT a purpose of exhaust ventilation in a refrigeration machinery room?
- Supplying conditioned air to the occupied floors above the room
- Removing the heat given off by the compressors and motors in the room
- Diluting escaped refrigerant vapor before concentrations can rise
- Moving escaped refrigerant vapor out of the room to the outdoors
Exhaust ventilation in a machinery room removes equipment heat, dilutes escaped refrigerant vapor, and moves it outdoors. It does not supply conditioned air to other floors; that is the job of the air distribution system, not a dedicated machinery room exhaust.